Measuring ranges | Smallest measuring range: 0…500 mbar |
| Largest measuring range: 0…50 bar |
| Negative pressure measuring range: up to -1 bar |
Analog output | 4…20 mA, 3-wires |
Contact output | DC PNP, max. 200 mA |
Power supply | 20 mA output: 19…30 V DC |
Accuracy | ≤ ± 0,5 % FS @ 25 °C |
Long term stability | ≤ ± 0,5 % FS / Year |
Response time | 50 ms - others on request |
Swich-on time | < 1 s |
Temperature coefficient | Zero: ≤ ± 0,03 % FS / Kelvin |
| Span: ≤ ± 0,02 % FS / Kelvin |
Medium temperature | -25…100 °C |
Surrounding temperature | -25…85 °C |
Storage temperature | -40…85 °C |
Short-circuit resistance | Permanent |
Reverse polarity protection | Protection against reverse polarity, but no function |
Electromagnetic compatibility | Interference emissions and immunity acc. to EN 61326 |
Wetted materials | Process connection: Stainless steel 1.4404 |
| Sensor: Ceramic Al2O3 |
| Sensor seal: FPM (Viton), NBR, EPDM, FFKM (Chemraz / Kalrez) |
Protection type | IP 67 |
Electrical connection | Cable gland M16x1,5 |
| Connector M12x1, 4-pole |
Weight | Approx. 300 g |